Configuring a Raritan PX2-5260A4R: Difference between revisions
		
		
		
		Jump to navigation
		Jump to search
		
 Created page with "{{howto_header}}  Tested against a Raritan PX2-5260R.    {{footer}}"  | 
				No edit summary  | 
				||
| Line 1: | Line 1: | ||
{{howto_header}}  | {{howto_header}}  | ||
{{warning|1=These are very raw notes.}}  | |||
Tested against a Raritan PX2-5260R.  | Tested against a Raritan PX2-5260R.  | ||
= Reset to defaults =  | |||
{{note|1=You must connect to the PDU using the RS232 (DB9) port. The USB port shuts down as part of the reset process and you'll not be able to factory reset!}}  | |||
# Connect to the RS232 port using: [<span class="code">screen /dev/ttyUSB0 115200</span>] (or your serial port device path is)  | |||
# Using pin, press the recessed 'Reset' switch and then immediately start pressing <span class="code"><esc></span> on your keyboard until the: [<span class="code">=> _</span>] prompt appears.  | |||
# Enter: [<span class="code">defaults</span>] and the system will reset to factory defaults. Be patient! It takes a couple of minutes.  | |||
# Log in with the default user name: [<span class="code">admin</span>] and the default password: [<span class="code">raritan</span>].   | |||
# Once logged in, you will be prompted to enter a new password.  | |||
= Configure an IP address =  | |||
You use either a standard USB A/B cable or a standard RS232 serial cable plugged into the DB9 port.  | |||
* With the B-side plugged into the PDU and the A-side connected to you computer. With will appear as: [<span class="code">/dev/ttyASM0</span>] on linux with no further driver needed. Connect with: [<span class="code">screen /dev/ttyASM0</span>] (no baud rate needs to be set).  | |||
* With the RS232 DB9 cable, use your serial device's address (ie: '<span class="code">/dev/ttyUSB0</span>', '<span class="code">/dev/tty0</span>', etc) to connect using: [<span class="code">screen /dev/ttyUSB0 115200</span>] (note that the baud rate must be set).  | |||
# Log into the PDU  | |||
# Enter: [<span class="code">config</span>]  | |||
# Enter: [<span class="code">network ipv4 ipConfigurationMode static ipAddress 10.20.2.1 subnetMask 255.255.0.0 gateway 10.20.255.254 primaryDNSServer 8.8.8.8 secondaryDNSServer 8.8.4.4</span>]  | |||
# Enter: [<span class="code">apply</span>]  | |||
# Enter: [<span class="code">reset unit</span>]  | |||
The unit will reboot and then you can log into the UI.  | |||
{{note|1=You must connect using '<span class="code">[[https]]</span>' on port 443! (ie: <span class="code">https://10.20.2.1</span>). It does not listen for a connection on standard <span class="code">[[http]]</span>'.}}  | |||
<span class="code"></span>  | |||
{{footer}}  | {{footer}}  | ||
Revision as of 21:50, 11 November 2015
| 
 Alteeve Wiki :: How To :: Configuring a Raritan PX2-5260A4R  | 
| Warning: These are very raw notes. | 
Tested against a Raritan PX2-5260R.
Reset to defaults
| Note: You must connect to the PDU using the RS232 (DB9) port. The USB port shuts down as part of the reset process and you'll not be able to factory reset! | 
- Connect to the RS232 port using: [screen /dev/ttyUSB0 115200] (or your serial port device path is)
 - Using pin, press the recessed 'Reset' switch and then immediately start pressing <esc> on your keyboard until the: [=> _] prompt appears.
 - Enter: [defaults] and the system will reset to factory defaults. Be patient! It takes a couple of minutes.
 - Log in with the default user name: [admin] and the default password: [raritan].
 - Once logged in, you will be prompted to enter a new password.
 
Configure an IP address
You use either a standard USB A/B cable or a standard RS232 serial cable plugged into the DB9 port.
- With the B-side plugged into the PDU and the A-side connected to you computer. With will appear as: [/dev/ttyASM0] on linux with no further driver needed. Connect with: [screen /dev/ttyASM0] (no baud rate needs to be set).
 - With the RS232 DB9 cable, use your serial device's address (ie: '/dev/ttyUSB0', '/dev/tty0', etc) to connect using: [screen /dev/ttyUSB0 115200] (note that the baud rate must be set).
 
- Log into the PDU
 - Enter: [config]
 - Enter: [network ipv4 ipConfigurationMode static ipAddress 10.20.2.1 subnetMask 255.255.0.0 gateway 10.20.255.254 primaryDNSServer 8.8.8.8 secondaryDNSServer 8.8.4.4]
 - Enter: [apply]
 - Enter: [reset unit]
 
The unit will reboot and then you can log into the UI.
| Note: You must connect using 'https' on port 443! (ie: https://10.20.2.1). It does not listen for a connection on standard http'. | 
| Any questions, feedback, advice, complaints or meanderings are welcome. | |||
| Alteeve's Niche! | Alteeve Enterprise Support | Community Support | |
| © 2025 Alteeve. Intelligent Availability® is a registered trademark of Alteeve's Niche! Inc. 1997-2025 | |||
| legal stuff: All info is provided "As-Is". Do not use anything here unless you are willing and able to take responsibility for your own actions. | |||